SWASTIK SYNERGY ENGINEERING PVT. LTD.



                                                             Temperature Range:
     SYNERT 200 BAR / 300 BAR INERT GAS SYSTEM
                                                             The  components  are  designed  and  tested  to  operate  in  the
     SYNERT GAS SYSTEM is the safe, natural way to extinguish a fire.   temperature  range  -20  °C  to  50  °C  or  as  stated  in  separate
     SYNERT GAS SYSTEM is safer and more economical than any   component listings.
     other system on the market.
                                                             SYNERT Agents:
                                                             Under  normal  conditions  SYNERT  agents  is  an  odourless
     SYNERT GAS SYSTEM: THE LATEST TECHNOLOGY                colourless gas.

     SWASTIK SYNERGY has introduced an improvement in systems   SYNERT Gases do not support combustion, nor have an impact
     using IG-01,IG-55,IG-100,IG-541 as the extinguishing agent with   on the ozone layer, and has no global warming potential. Inert
     the latest technology, providing benefits to the facility itself and   Gases are supplied as under:
     the protected enclosure.
                                                               Name of Gas         Contents
     This innovative technology enables to optimize the design of the
                                                               SYNERT IG-01        Argon
     firefighting  system  with  IG-01,IG-55,IG-100,IG-541  as  the
                                                               SYNERT IG-55        50% Argon, 50% Nitrogen
     discharge pressure and flow control allow users to reduce the
     size of tubing needed for proper distribution of the agent and   SYNERT IG-100  Nitrogen
     reduce overpressure that take place in the protected enclosure,   SYNERT IG-541  52% Nitrogen, 40% Argon, 8% Co2
     minimizing the area for the relief of excess pressure.
                                                             Storage containers are designed to hold agent in gaseous form at
     SYNERT systems are designed to suppress fires involving class
                                                             a nominal pressure of 200 bar or 300 bar at 15 °C.
     A,  B  and  C  hazards.    The  systems  are  designed  to  be  total
                                                             Handling and Installation of SYNERT equipment should only be
     flooding and consist of a fixed supply of agent connected to a
                                                             carried out by persons experienced in dealing with this type of
     piping system with nozzles to direct the agent into an enclosed
                                                             equipment.  The  following  specification  applies  to  SYNERT
     hazard.  Inert  gas  extinguishes  fires  by  lowering  the  oxygen
                                                             agents:
     content  below  the  level  that  supports  combustion.  In  simple
     terms if the oxygen content of the atmosphere is reduced to a
     level below 15%, most ordinary combustibles will not burn. Since   SYNERT AGENT SPECIFICATION
     SYNERT agents are stored as a gas, it discharges as an invisible
     gas,  allowing  people  to  safely  exit  a  protected  space  without   Pressure
                                                                                   295 Bar – 300 Bar at 15° C
     obscured vision.                                          (300 Bar System)
     SYNERT gas systems are particularly valuable in extinguishing   Pressure
                                                                                   195 Bar – 200 Bar at 15° C
     fires  in  enclosures  containing  hazards  or  equipment  where  a   (200 Bar System)
     clean, electrically non-conductive medium is essential or where   Moisture    Max 12 ppm
     the cleaning up of foam, water or powder would be problematic.


                                                             HOW IS IT ACTUATED?
     MAXIMUM PROTECTION, MINIMUM STORAGE
                                                             The extinguishing principle of inert gases focuses on reducing
     SYNERT GAS SYSTEM containers allow you to protect single- or
                                                             oxygen concentration in the affected zone. When a fire starts
     multiple-hazard areas typically requiring less floor space than
                                                             SYNERT  Gases  rapidly  penetrates  the  area  and  reduces  the
     other inert gas systems.
                                                             oxygen level percentage from the usual level of 21% to a limit that
     Think of the cost savings!                              fluctuates  between  13%  and  11%,  the  amount  sufficient  for
     You  no  longer  need  to  purchase,  install  and  maintain  several   combustion to stop and to be safe for the people in the room. Due
     individual  protection  systems  for  your  multi-risk  facility.  One   to  the  stratification  of  the  gases,  protection  is  achieved
     SYNERT GAS SYSTEM does it all.                          throughout  the  space,  regardless  of  how  high  the  ceiling  is.
                                                             During  its  discharge,  there  is  excellent  visibility  and,  since  it
                                                             leaves  no  residue,  there  are  no  destructive  effects  to  the
                                                             equipment,  which  will  continue  functioning  normally  and,  of
                                                             course, there will be nothing to clean up.