Page 5 - Control Units, Releasing Device
P. 5
SWASTIK SYNERGY ENGINEERING PVT. LTD.
Electrical Specication
Power Releasing Agent Circuit
220-240 VAC, 50 Hz. Operating Nominal Voltage : 24 VDC
Wire size: 1.5 Sq. mm with 600V insulation Solenoid output : 0.75A
End-Of-Line Resistor : 4.7K, 1/4watt (for
Battery (Lead Acid only) Solenoid Output)
Charging Voltage : 28 VDC.
Charging Current : 0.5 Amps (Max) Remote Outputs
System Quiescent Current : 80mA Fire Contact (C, NO, NC) : 220v AC/30v DC@ 1A
Fault Contact (C, NO, NC) : 220v AC/30v DC@ 1A
Initiating Device Circuits (Zone Circuit)
All zones are Class B wiring Cross Zoning Contact(C, NO, NC) : 220v
Normal Operating Voltage: 14 - 21 VDC AC/30vDC@1A
Alarm Current : 15 - 30mA
Short Circuit Current : 40mA Maximum 24 VDC Power For remote devices (Optional)
Loop resistance : 50 ohms Maximum Operating Voltage : 24VDC, 500mA Max.
End-Of-Line Resistor : 4.7K, 1/4watt
Standby Current : 6.8mA
(2.4mA for Detectors) Operating Condition
Operating Temperature 0 - 49° C / 32-120° F.
Notication Appliance Circuits (Sounder / Strobe Circuit)
Relative Humidity 93 ± 2% RH (non-condensing) at
1) Supervised 32 ±2° C / 90 ± 3° F.
Operating Nominal Voltage : 24 VDC
Operating Current : 0.75A (Max)
End-Of-Line Resistor : 4.7K, 1/4watt
2) Non - Supervised
Operating Nominal Voltage : 24 VDC
Operating Current : 0.3A (Max)
End-Of-Line Resistor : 4.7K, 1/4watt
Mounting Detail: ø19
30 30
30 30
Note:- All Dimensions are in MM
35
200
Mechanical Specication:
Dimensions : (400W X 300H X 100D)
Color : Red / White
Construction : 18 Gauge (1.22mm) CRCA sheet with powder-coated Finish
IP Rating : IP50
Cable Entry : 09 x ø19mm Knockout in top of the cabinet